142
Reference Manual
00809-0100-4021, Rev JA
Configuration
April 2017
Configuration
4.5.3 Recommended actions for Plantweb alerts
RECOMMENDED_ACTION
The RECOMMENDED_ACTION parameter displays a text string that gives a recommended course of
action based on the type and specific event of the Plantweb alerts are active.
Table 4-2. RB.RECOMMENDED_ACTION
Alarm type
Failed/maint/advise
active event
Recommended action
text string
Plantweb alerts
None None No action required
Advisory NV Writes Deferred
Non-volatile writes have been deferred, leave the device
powered until the advisory goes away
Maintenance
Configuration Error Re-write the Sensor Configuration
Primary Value
Degraded
Confirm the operating range of the applied sensor and/or
verify the sensor connection and device environment
Calibration Error Retrim the device
Secondary Value
Degraded
Verify the ambient temperature is within operating limits
Failed
Electronics Failure Replace the Device
HW / SW Incompatible
Verify the Hardware Revision is compatible with the
Software Revision
NV Memory Failure Reset the device then download the Device Configuration.
Primary Value Failure
Verify the instrument process is within the Sensor range
and/or confirm sensor configuration and wiring.
Secondary Value
Failure
Verify sensor range and/or confirm sensor configuration
and wiring
Diagnostic Error
Sensor Drift Alert or
Hot BU active
Confirm the operating range of the supplied sensor and/or
verify the sensor connection and device environment
Primary Value
Degraded
Confirm the operating range of the supplied sensor and/or
verify the sensor connection and device environment