88
Reference Manual
00809-0100-4021, Rev JA
HART Commissioning
April 2017
HART Commissioning
3.8 Rosemount X-well Technology configuration
Rosemount X-well functionality can easily be enabled and configured via a field communicator or asset
management system. The Rosemount 3144P Temperature Transmitter can be ordered with Rosemount
X-well technology via the “PT” model option code. The”C1” model option code must be ordered if the
“PT” option code is specified. The “C1’ option code requires user supplied information of process pipe
material and pipe schedule. Rosemount X-well technology can be configured with any asset
management software that supports Electronic Device Description Language (EDDL). The Device
Dashboard interface with DD revision 3144P Dev. 7 Rev. 1 or higher is required to view Rosemount X-well
functionality. The “Rosemount X-well Process” sensor/type option should be selected as the sensor type
in most cases. Once selected, pipe material, line size, and pipe schedule information is required when
configuring Rosemount X-well technology. This section is referring to the process pipe properties that
Rosemount 3144P and 0085 Pipe Clamp Sensor with Rosemount X-well technology is going to be
installed in. This information is required for the in-transmitter algorithm to accurately calculate process
temperature. In the rare case that the process pipe is not available, a custom value for the pipe
conduction coefficient can be entered. This field becomes available when the “Rosemount X-well
Custom” sensor/type option is selected.
3.8.1 Configure Rosemount X-well technology with a Field
Communicator
Perform the following procedure:
1. From the Home screen, select 2: Configure.
2. Select 1: Guided Setup.
3. Select 1: Configure Sensor.
4. Select 1: Configure Sensor Type and Units.
5. Select either Rosemount X-well Process or Rosemount X-well Custom.
6. Select desired configurations and select Enter.
Configure Rosemount X-well Technology in manual setup: Fast Keys
2-2-1-11
1. Under Configure Sensors, select Rosemount X-well Process sensor type.