41
Reference Manual
00809-0100-4021, Rev JA
HART Commissioning
April 2017
HART Commissioning
3.7.3 Change type and connections
The connections command allows the user to select the sensor type and the number of sensor wires to
be connected from the following list:
2-, 3-, or 4-wire Pt 100, Rosemount X-well, Pt 200, Pt 500, Pt 1000
(platinum) RTDs (α = 0.00385 Ω/Ω/°C)
2-, 3-, or 4-wire Pt 100, Pt 200 (platinum) RTDs (α = 0.003916 Ω/Ω/°C)
2-, 3-, or 4-wire Ni 120 (nickel) RTDs
2-, 3-, or 4-wire Cu 10 (copper) RTDs
IEC/NIST/DIN Type B, E, J, K, R, S, T thermocouples
DIN type L, U thermocouples
ASTM Type W5Re/W26Re thermocouple
GOST Type L thermocouples
–10 to 100 millivolts
2-, 3-, or 4-wire 0 to 2000 ohms
Contact an Emerson representative for information on temperature sensors, thermowells, and accessory
mounting hardware that is available through Emerson.
3.7.4 Output units
The snsr 1 unit and snsr 2 unit commands set the desired primary variable units. The transmitter output
can be set to one of the following engineering units:
Degrees Celsius
Degrees Fahrenheit
Degrees Rankine
Kelvin
Ohms
Millivolts
3.7.5 Sensor 1 serial number
The serial number of the attached sensor can be listed in the sensor 1 S/N variable. It is useful for
identifying sensors and tracking sensor calibration information.
HART 5 Fast Keys
Sensor 1: 2, 2, 1
Sensor 2: 2, 2, 2
HART 7 Fast Keys
Sensor 1: 2, 2, 1
Sensor 2: 2, 2, 2
HART 5 Fast Keys
Sensor 1: 2, 2, 1, 4
Sensor 2: 2, 2, 2, 4
HART 7 Fast Keys
Sensor 1: 2, 2, 1, 5
Sensor 2: 2, 2, 2, 5
HART 5 Fast Keys
2, 2, 1, 7
HART 7 Fast Keys
2, 2, 1, 8