Installation
April 2017
Installation
2.3.2 Set the switches
HART
Without an LCD display
1. If the transmitter is installed in a loop, set the loop to manual mode and disconnect the power.
2. Remove the housing cover on the electronics side of the transmitter. Do not remove the transmitter
cover in explosive atmospheres with a live circuit.
3. Set the switches to the desired position (see Figure 2-3 on page 12).
4. Replace the transmitter cover. Both transmitter covers must be fully engaged to meet
explosion-proof requirements.
5. Apply power and set the loop to automatic mode.
With an LCD display
1. If the transmitter is installed in a loop, set the loop to manual mode and disconnect the power.
2. Remove the housing cover on the electronics side of the transmitter. Do not remove the transmitter
cover in explosive atmospheres with a live circuit.
3. Unscrew the LCD display screws and gently slide the meter straight off.
4. Set the switches to the desired position (see Figure 2-3 on page 12).
5. Gently slide the LCD display back into place, taking extra precautions with the 10 pin connection.
6. Replace and tighten the LCD display screws to secure the LCD display.
7. Replace the transmitter cover. Both transmitter covers must be fully engaged to meet
explosion-proof requirements.
8. Apply power and set the loop to automatic mode.
FOUNDATION Fieldbus
Without an LCD display
1. If the transmitter is installed in a loop, set the loop to Out-of-Service (OOS) mode (if applicable) and
disconnect the power.
2. Remove the housing cover on the electronics side of the transmitter. Do not remove the transmitter
cover in explosive atmospheres with a live circuit.
3. Set the switches to the desired position (see Figure 2-2).
4. Replace the transmitter cover. Both transmitter covers must be fully engaged to meet
explosion-proof requirements.
5. Apply power and set the loop to In-Service mode.