Figure 8-29: Input Selector Function Block Schematic
A. Selection algorithm
B. Out
C. Selector
8.12.1  Block errors
Table 8-31 lists the conditions reported in the BLOCK_ERR parameter.
Table 8-31: Block Error Conditions
Condition
number
Condition name and description
0 Other: The output has a quality of Uncertain.
1 Block Configuration Error
2 Link Configuration Error
3 Simulate Active
4 Local Override: The actual mode is LO.
5 Device Fault State Set
6 Device Needs Maintenance Soon
7 Input Failure/Process Variable has Bad Status: One of the inputs is bad
or not connected.
8 Output Failure: The output has the quality of Bad.
9 Memory Failure: A memory failure has occured in FLASH, RAM or
EEROM memory.
10 Lost Static Data
11 Lost NV Data
12 Readback Check Failed