2. From the Start menu, select DeltaVEngineeringDeltaV Explorer.
3. Select/expand Library (right below DeltaV system).
4. Right-click Fieldbus Devices. This brings up a list of options.
5. From the list, select Add Device Definition. This opens a Browse for folder
dialog box. Browse to the directory that contains the seven files needed to
register a new device with DeltaV. These files consist of 3 *.dll files, *.sym,
*.ffo, *fhx, and *.reg files. The files are probably on a floppy disk or a CD-
ROM that accompanies your device. On CD-ROMs delivered together with
Emerson transmitters the files are located in the directory /Fieldbus.
Dependent on the existing system, use the files of the appropriate
subdirectory.
6. Answer Yes to the first prompt. DeltaV starts the installation.
Figure 8-33 shows the Exploring DeltaV screen for reference.
Figure 8-33: DeltaV Explorer
FOUNDATION
Fieldbus Manual
December 2022 00809-0500-4880