4.2 Auto Operation
1. Check that the mains is connected to the unit and is present.
2. Check the mains voltage readings on the display.
3. At the EAOM-210 FLJ, press the Auto (27) button. The LED (10) on the button should
light.
4. Switch off the mains supply to the unit. Check that the generator starts and, after a
delay, the load is transferred to the generator.
5. Restore the mains supply to the unit. Check that, after a delay, the load is transferred
back to the mains and the generator, after a further delay, shuts down.
4.3 Test Mode Operation
1. Check that the mains is connected to the unit.
2. Press the Test (28) button. At this moment the LED (11) will light on.
3. Check that the generator starts and that the load is still connected to the mains.
4. Switch off the mains supply. Check that the contactors change over to connect the load
to the generator. Check also that the Auto (10) LED is lit. The unit changes operating mode
to AUTO Mode automatically.
5. Restore the mains supply. Check that the contactors reconnect the load to the mains
supply.
6. Check that the generator shuts down with cool-down period.