EAOM-210 FLJ.eng / ver 0.0
Pages 130 / 132
Section 8 Specifications & Ratings
Specification: Description:
Equipment use Electrical control equipment for generating sets
Housing & Mounting 144 mm x 204 mm x 37 mm. (including connectors
housing for panel mounting.
Panel Cut-Out 138 mm x 186 mm.
Protection IP54 at front panel, IP20 at rear side.
Weight Approximately 0,76 Kg.
Environmental rating Standard, indoor at an altitude of less then 2000 meters with
non-condensing humidity.
Operating / Storage
Temperature
0°C to +50°C / -25°C to +70°C
Operating / Storage
Humidity
90 % max. (non-condensing)
Installation Over Voltage
Category
II Appliances, portable equipment.
Pollution Degree II, Normal office or workplace, non conductive pollution
Mode of Operation Continuous
EN 61000-6-4, EMC Generic Emission Standard for industrial
equipment
EMC
EN 61000-6-2, EMC Generic Immunity Standard for industrial
equipment
Electrical Safety EN 61010-1, Safety Requirements for electrical equipment for
measurement, control and laboratory use
DC Battery Supply
Voltage
8 to 32 VDC max. operating current is 360 mA.
Cranking Dropouts Battery voltage can be “0” VDC for max. 100 ms during cranking
(battery voltage should be at least nominal voltage before
cranking).
Battery Voltage
Measurement
8 to 32 VDC, accuracy: 1 % FS, resolution: 0,1 V
Mains Voltage
Measurement
Selectable three phase or single phase, 4 wire connection for
three phase, 2 wire connection for single phase gen-set. 35 to
300 VAC Ph-N, 15.6 to 99.9 Hz. Accuracy: 1 % FS, Resolution: 1 V
Mains Frequency 15.6 to 99.9 Hz (min. 35 VAC Ph-N) Accuracy: 0,25 % FS,
Resolution: 0,1 Hz.
Generator Voltage
Measurement
Selectable three phase or single phase, 4 wire connection for
three phase, 2 wire connection for single phase gen-set. 35 to
300 VAC Ph-N, 15.6 to 99.9 Hz. Accuracy: 1 % FS, Resolution: 1 V
Generator Speed From magnetic pick-up: 35 to 10000 Hz (4 to 35 volts peak
continuously.) Accuracy: 0,25 % FS
Generator Frequency From alternator voltage: 15.6 to 99.9 Hz (min. 35 VAC Ph-N)
Accuracy: 0,25 % FS, Resolution: 0,1 Hz.
CT secondary 5A.
Charge Generator
Excitation
220mA, max 4W.