3.5 Programmable function definitions
Operator parameters
(MAINS LEVELS PAGE) MAINS LEVELS page
MAINS UNDER VOLTAGE Mains Under Voltage
VAC 60 – 600 320
MAINS UNDER V.RET. Mains Under Voltage Return
VAC 60 – 600 340
MAINS OVER VOLTAGE Mains Over Voltage
VAC 60 – 600 440
MAINS OVER V.RETURN Mains Over Voltage Return
VAC 60 – 600 420
MAINS UNDER FREQ. Mains Under Frequency
Hz 20.0 – 75.0 45.0
MAINS UNDER F.RET. Mains Under Frequency Return
Hz 20.0 – 75.0 48.0
MAINS OVER FREQ. Mains Over Frequency
Hz 20.0 – 75.0 55.0
MAINS OVER F.RETURN Mains Over Frequency Return
Hz 20.0 – 75.0 52.0
The unit uses these parameters to decide when to lit the “Mains Okey LED”.
In Automatic mode, the unit uses these parameters to switch the load between the mains
supply and the alternator.
(GEN.VOLT.LEVELS PAGE) GENERATOR VOLTAGE LEVELS page
GEN.UNDER VOLTAGE Generator Under Voltage
VAC (dis)60 – 600 320
GEN.UNDER V.PRE-ALR Generator Under Voltage Pre-Alarm
VAC (dis)60 – 600 340
GEN.LOADING VOLTAGE Generator Loading Voltage
VAC 60 – 600 345
GEN.OVER V.PRE-ALR Generator Over Voltage Pre-Alarm
VAC (dis)60 – 600 420
GEN.OVER V.PR-A.RET Generator Over Voltage Pre-Alarm Return
VAC 60 – 600 400
GEN.OVER VO.SHUTDWN Generator Over Voltage Shutdown
VAC 60 – 600 440
The unit uses these parameters to decide when to display Voltage Failure and Voltage Error
Messages. Also, the unit uses Generator Loading Voltage parameter to decide when to take
the load.
(GEN.FREQ.LEVELS PAGE) GENERATOR FREQUENCY LEVELS page
GEN.UNDER FREQUENCY Generator Under Frequency
Hz (dis)30.0 – 75.0
43.0
GEN.UNDER F.PRE-ALR Generator Under Frequency Pre-Alarm
Hz (dis)30.0 – 75.0
45.0
GEN.LOADING FREQ. Generator Loading Frequency
Hz 30.0 – 75.0 46.0
GEN.OVER F.PRE-ALR Generator Over Frequency Pre-Alarm
Hz (dis)30.0 – 75.0
55.0
GEN.OVER F.PR-A.RET Generator Over Frq Pre-Alarm Return
Hz 30.0 – 75.0 54.0
GEN.OVER FR.SHUTDWN Generator Over Frequency Shutdown
Hz (dis)30.0 – 75.0
58.0
The unit uses these parameters to decide when to display Speed Failure and Frequency
Error Messages. Also, the unit uses Generator Loading Frequency parameter to decide
when to take the load.
(GEN.CUR/POW.LVL.PAGE) GENERATOR CURRENT/POWER LEVELS page
GEN.OVER CURRENT Generator Over Current
A AC 0 – 9999 9999
GEN.SHORT CIRCUIT Generator Short Circuit
A AC 0 – 9999 9999
GEN.EARTH FAULT Generator Earth Fault
A AC 0 – 9999 100