EAOM-210 FLJ.eng / ver 0.0
Pages 36 / 132
Technician parameters
(GEN.CUR/POW.ACT.PAGE) GENERATOR CURRENT/POWER ACTIONS page
CT PRIMARY CT Primary
A AC 0 – 9999 500
EARTH FAULT CT PRIM CT Primary (Earth Fault)
A AC 0 – 9999 500
OVER CUR.ACTIONS
Over Current Actions
-Disable
-Warning (Alarm Only, No Shutdown)
-Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
-Shutdown (Alarm And Shutdown)
-
0-3 dis
OVER CUR.ALARM TIME Over Current Alarm Time
Sec 0 - 99 0
SHORT CIR.ACTIONS
Short Circuit Actions
-Disable
-Warning (Alarm Only, No Shutdown)
-Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
-Shutdown (Alarm And Shutdown)
-
0-3 dis
SHORT CIR.ALRM TIME Short Circuit Alarm Time
Sec 0 - 99 0
EARTH FAULT ACTIONS
Earth Fault Actions
-Disable
-Warning (Alarm Only, No Shutdown)
-Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
-Shutdown (Alarm And Shutdown)
-
0-3 dis
EARTH FAU.ALRM TIME Earth Fault Alarm Time
Sec 0 - 99 0
(MISCELLANEOUS PAGE) MISCELLANEOUS page
SENS.OPT.GEN.F.ENAB Sensing Options Generator Frq En/Dis
-
ENAB DIS ENAB
SNS.OP.PICKP ENA&FW Sensing Opt Pickup En/Dis & Flywheel
-
(dis)0-1000 DIS
AC SYSTEM
Ac System:
0= 1phase 2wire,
1= 3phase 4wire,
2= 3phase 4wire Series Delta,
3= 1phase 3wire
-
0-3 1
FAST LOAD.FEAT.ENAB Fast Loading Feature En/Dis
-
ENAB DIS DIS
ALL WRN.ARE LTCH.EN All Warnings Are Latched En/Dis
-
ENAB DIS DIS
MAINS FAIL.DETEC.EN Mains Failure Detection En/Dis
-
ENAB DIS ENAB
LK.MA.FA.FO.MA.CN.E
Look Mains Failure For Mains Cont.
En/Dis
-
ENAB DIS DIS
GAS/DIESEL SELECT Engine Fuel (Gas/ Diesel) Selection
-
GAS/ DIESEL
DIESEL
STOP/FUEL SELECTION Stop / Fuel Selection
-
STOP/FUEL FUEL
STOP SOLENOID TIME Stop Solenoid Time
Sec 5 - 99 20
IGNITION DELAY Ignition Delay
Sec 1 - 99 5
GAS VALVE DELAY Gas Valve Delay
Sec 1 - 99 5
MIN.IGNITION SPEED Min Ignition Speed
RPM 10 - 1500 200
NOMINAL FREQUENCY Nominal Alternator Frequency
Hz 30.0 – 75.0 50.0
NOMINAL SPEED Nominal Speed
RPM 500 - 5000 3000
VOLT TRANSFRM RATIO Voltage Transformer Ratio
1 - 50 1
SENSING OPTIONS GENERATOR FRQ EN/DIS:
ENABLE: Speed sensing will be derived from the generator output frequency.
DISABLE: Speed sensing not will be derived from the generator output frequency.
SENSING OPT. PICKUP EN/DIS & FLYWHEEL
DISABLE: Speed sensing will not be derived from the magnetic pickup.
1-1000: Speed sensing will be derived from the magnetic pickup and the number is flywheel
teeth on the engine.