Table 2.2 Unit wiring description
Pin Function
1 L1
2 L2
3 L3
Mains voltage inputs. Used to detect failure for controlling automatic transfer of load
to alternator. Pins 2 and 3 not used on single phase applications.
4 Mains voltage neutral
5 L1
6 L2
7 L3
Alternator voltage inputs. Unit can be programmed to use frequency of alternator
output to detect when engine has started. Pins 6 and 7 not used on single phase
applications.
8 Alternator voltage neutral
9 Not connected
10 Fuel level sender
11 Coolant temperature sender
12 Low oil pressure sender
13 Magnetic input +ve. An AC signal from the magnetic pick-up +ve for speed sensing.
14 Magnetic input –ve. An AC signal from the magnetic pick-up -ve for speed sensing.
15 Input from charge generator. Can be used to detect when engine has started.
16
Configurable input-6. This is a negative switched configurable input, see Digital
Configurable Input-6 Page Section for options available. It is possible to configure input to
be a normally closed signal or a normally open signal.
17
High Temperature or Configurable input-5. This is a negative switched. If Configurable
input-5 is not selected as High Temperature, It is possible to configure input to be a
normally closed signal or a normally open signal. See Digital Configurable Input-5 Page
Section for options available.
18
Low Oil Pressure or Configurable input-4. Normally closed contact. Switch to 0V. If
Configurable input-4 is not selected as Low Oil Pressure, It is possible to configure input to
be a normally closed signal or a normally open signal. See Digital Configurable Input-4 Page
Section for options available.
19
Configurable input-3. This is a negative switched configurable input, see Digital
Configurable Input-3 Page Section for options available. It is possible to configure input to
be a normally closed signal or a normally open signal.
20
Configurable input-2. This is a negative switched configurable input, see Digital
Configurable Input-2 Page Section for options available. It is possible to configure input to
be a normally closed signal or a normally open signal.
21
Configurable input-1. This is a negative switched configurable input, see Digital
Configurable Input-1 Page Section for options available. It is possible to configure input to
be a normally closed signal or a normally open signal.
22
Input from emergency stop switch. Normally closed contact. Switch to 0V. when the switch
is opened, the engine is stopped.
23
Mains Contactor Open Relay Output. See Breakers Page Section for options available. Volts
free contacts to 24.
24
Mains Contactor Open Relay Output. See Breakers Page Section for options available. Volts
free contacts to 24.
25
Mains Contactor Close Relay Output. See Breakers Page Section for options available. Volts
free contacts to 26.
26
Mains Contactor Close Relay Output. See Breakers Page Section for options available. Volts
free contacts to 25.
27
Gen. Contactor Open Relay Output. See Breakers Page Section for options available. Volts
free contacts to 28.
28
Gen. Contactor Open Relay Output. See Breakers Page Section for options available. Volts
free contacts to 27.