29
Gen. Contactor Close Relay Output. See Breakers Page Section for options available. Volts
free contacts to 30.
30
Gen. Contactor Close Relay Output. See Breakers Page Section for options available. Volts
free contacts to 29.
31
Output to fuel / stop relay. DC supply from Pin 32. Controls fuel to engine or controls
engine stopping.
32 +Battery supply input. Supplies to Pin 31,33,34
33 Output to start relay. DC supply from Pin 32. Controls starter motor.
34
Horn or configurable relay output-1. DC supply from Pin 32. See Configurable Output-1 Page
Section for options available.
35 +Battery supply input. Supplies to Pin 36,37,38
36
Configurable relay output-2. DC supply from Pin 35. See Configurable Output-2 Page Section
for options available.
37
Configurable relay output-3. DC supply from Pin 35. See Configurable Output-3 Page Section
for options available.
38
Configurable relay output-4. DC supply from Pin 35. See Configurable Output-4 Page Section
for options available.
39 - Battery input supplies EAOM-210 FLJ
40 + Battery input supplies EAOM-210 FLJ
41 CT Secondary for Earth current (IEA).
42 CT Secondary for Earth current (IEA).
43 CT Secondary for load L3.
44 CT Secondary for load L2.
45 CT Secondary for load L1.
46 CT Secondary for load common.

Table of Contents