EAOM-210 FLJ.eng / ver 0.0
Pages 84 / 132
REMOTE STOP DELAY
This timer dictates how long the module will wait after it has received a remote stop signal
before it will attempt to stop. This prevent un-necessary stopping on a fluctuating mains
supply etc.
PRE-HEAT
This timer dictates the duration that the pre-heat output will be active before an attempt is
made to start the engine. Once this timer is expired cranking will commence.
PRE-HEAT BYPASS
This feature allows the module to start a hot engine without performing an un-necessary pre-
heat delay. The bypass timer is triggered by the generator starting and actually being loaded.
If the generator started but does not achieve loading then the timer will not be triggered. The
bypass timer is initiated once the engine has come to rest. If any attempts to start are
requested within the duration of the bypass timer the start sequence will bypass the pre-heat
timer.
SAFETY ON DELAY
This timer dictates how long the module will ignore the Low Oil Pressure, High Engine
Temperature, Under speed, Under volts and any other inputs configured as active from
safety on. It allows the values such as oil pressure to rise to their operating values on starting
without triggering an alarm. Once the timer has expired all alarm conditions are monitored
again. If configured to use ‘fast loading’, should all the monitored conditions, such as oil
pressure, come to expected state prior to the end of the safety on timer, the timer will be
terminated prematurely ensuring maximum protection as soon as possible.
HORN DURATION
This timer dictates how long the horn will work after the last error detected. Once after this
timer ended module will do horn reset.
CHARGE EXCITATION TIME
Charge excitation was selectable as momentary / continuous operation.This timer dictates
how long the Charge excitation will active.
COOLING FAN TIME
This timer dictates how long the Cooling Fan will continue to operate.
MAINS FAIL DELAY
The unit uses this parameter to decide the mains fail.
(LOAD/STP.TIMERS PAGE) LOAD/STOPPING TIMERS page
WARM UP TIME Warmup Timer
Sec 0 - 250 3
RETURN DELAY Return Delay
Sec 0 – 3600 5
COOLING TIME Cooling Timer
Sec 0 – 9999 60
GEN.FR.ERR.CNT.TIME Generator Frequency Error Control Time
Sec 0.0 – 10.0 1.0
GEN.VL.ERR.CNT.TIME Generator Voltage Error Control Time
Sec 0.0 – 10.0 1.0
FAIL TO STOP TIME Fail To Stop Time
Sec 15 – 99 30
WARMUP TIMER
This timer is initiated once the engine is up and running. It delays loading the generator until
it has stabilised. Once this timer is expired the ‘Close generator’ signal will be given and the
generator is available to be loaded.