EasyManua.ls Logo

Emotron M20 - Three-Phase Connection Example; Selection of Current Transformer; For Motors Under 100 A

Emotron M20
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CG Drives & Automation 01-5958-01r0
Fig. 1 Connection example
Please use the enclosed plastic (rubber) insert (if ordered, optional) to cover the
monitor terminals.
NOTE: If the START/STOP is connected as per Fig. 1, it is recommended that
terminals 6 and 7 be bypassed during programming. After the programming
is completed the bypass must be taken out. Make sure that the monitor
voltage range e.g. 3x380-500 VAC matches the connected motor/line
voltage, e.g. 3x 400 V.
M20
A+ A-
R1
R2
C
L1
L3
L2
S2S1
DIG
{
L1
L2
L3
K1
U
V
W
M
K1
K1
3
4
9
11
13
1
2
6
7
8
5
Stop
Start
N (alt. 48 VDC+)
Max. 240 VAC (alt. 0 VDC-)
NOTE: in power down,
both relays are alwas
N.O.
Please see CTM
information
on Page 11.
NOTE: Monitor
voltage see
Note below.

Related product manuals