Installation Cerabar M HART
10 Endress+Hauser
3.3.1 Installation instructions for devices without a diaphragm seal –
PMC41, PMC45, PMP41, PMP45
!
Note!
If a heated Cerabar M is cooled during a cleaning process (e.g. by cold water), a vacuum develops
for a short time, whereby moisture can penetrate the sensor through the pressure compensation
. If this is the case, mount the Cerabar M with the pressure compensation pointing
downwards.
Keep the pressure compensation and GORE-TEX
®
filter free from dirt.
Cerabar M devices without diaphragm seals are mounted as per the norms for a manometer
(DIN EN 839-2). We recommend the use of shutoff devices and siphons. The orientation depends
on the measuring application.
Do not clean or press the diaphragm with hard or pointed objects.
Pressure measurement in gases
P01-PMx4xxxx-11-xx-xx-xx-002
Fig. 3: Measuring arrangement for pressure measurement in gases
Cerabar M
Shutoff device
Mount Cerabar M with shutoff device above the tapping point so that the condensate can flow
into the process.