3 Installation
3.1 Incoming acceptance and storage
3.1.1 Incoming acceptance
• Check the packaging and the contents for damage.
• Check the shipment, make sure nothing is missing and that the scope of supply matches your
order.
3.1.2 Storage
The device must be stored in a dry, clean place and protected against damage from impact
(EN 837-2).
Storage temperature range:
• –40 to +100°C (–40 to +212°F)
• Onsite display: –40 to +80°C (–40 to +176°F)
3.2 Installation conditions
3.2.1 Dimensions
→ For dimensions, please refer to the Technical Information for Cerabar M TI399P, "Mechanical
construction" section.
3.3 Installation instructions
!
Note!
• Due to the orientation of the Cerabar M, there may be a shift in the zero point, i.e. when the
container is empty, the measured value does not indicate zero. The position-dependent zero point
shift can be corrected directly at the device via 2 keys → see Page 29, Section 6.2.5 "Position
adjustment - only display (bias pressure)" (onsite operation) or via communication → see Page 33,
Section 6.3.7 "Position adjustment - only display (bias pressure)".
• For PMP46 and PMP48, please pay attention to Page 13, Section 3.3.2 "Installation instructions
for devices with diaphragm seals – PMP46, PMP48".
• The onsite display can be rotated in 90° stages.
• Endress+Hauser offers a mounting bracket for installation on pipes or walls.
(→ See Page 16, Section 3.3.4 "Wall and pipe-mounting (optional)").