Operation Cerabar M HART
24 Endress+Hauser
5.2 Operating elements
5.2.1 Position of the operating elements on the electronic insert
The onsite display is supplied ready-mounted if it is ordered with the device. In such instances, the
onsite display with the retaining ring must be released from the electronic insert before operating.
Removing the display:
Push up the latch with the arrow until the grip of the retaining ring on the electronic insert is
audibly released.
Release the retaining ring and lift off carefully to prevent damage to the display cables.
During operation, you can fit the display onto the edge of the housing.
P01-PMx4xxxx-19-xx-xx-xx-025
Fig. 27: Position of operating elements
Switch for damping on/off
Key for calibrating the lower-range value (Zero = Lower-range value (LRV))
Key for calibrating the upper-range value (Span = Upper-range value (URV))
Terminal lugs for measuring the signal current
+
+
Zero
Damping
on off
Span
Display
3
4