Installation Cerabar M PMC51, PMP51, PMP55
12 Endress+Hauser
A0028472
Pressure measurement in gases
Mount the Cerabar M with the shutoff device above the tapping point so that any condensate
can flow into the process.
Pressure measurement in vapors
Mount the Cerabar M with the siphon below the tapping point.
Fill the siphon with liquid before commissioning. The siphon reduces the temperature to
almost ambient temperature.
Pressure measurement in liquids
Mount the Cerabar M with the shutoff device below or at the same level as the tapping point.
Level measurement
Always install the device below the lowest measuring point.
Do not install the device at the following positions:
in the filling curtain
in the tank outlet
in the suction area of a pump
at a point in the tank which could be affected by pressure pulses from the agitator.
The calibration and functional test can be carried out more easily if you mount the device
downstream from a shutoff device.