Commissioning Cerabar M PMC51, PMP51, PMP55
28 Endress+Hauser
Setting lower pressure value
1 Desired pressure for lower pressure value ("empty pressure") is present at device.
2 Press the "Zero" key for at least 3 s.
3 Does the LED on the electronic insert light up briefly?
4 Yes No
5 The pressure present was saved as the lower pressure value
("empty pressure") and assigned to the lower level value
("empty calibration").
Applied pressure was not saved as the lower
pressure value. Observe the input limits.
Setting upper pressure value
1 Desired pressure for upper pressure value ("full pressure") is present at device.
2 Press the "Span" key for at least 3 s.
3 Does the LED on the electronic insert light up briefly?
4 Yes No
5 The pressure present was saved as the upper pressure value
("full pressure") and assigned to the upper level value ("full
calibration").
Applied pressure was not saved as the upper
pressure value. Observe the input limits.
8.3 Commissioning with an operating menu
Commissioning comprises the following steps:
• Function check
• Selection of the language, measuring mode and pressure unit → 28
• Position adjustment/zero adjustment → 30
• Configuring measurement:
• Pressure measurement → 31
• Level measurement → 31
8.3.1 Selecting the language, measuring mode and pressure unit
Language (000)
Navigation Main menu → Language
Write permission Operators/Service engineers/Expert
Description Select the menu language for the local display.