Commissioning Cerabar M PMC51, PMP51, PMP55
30 Endress+Hauser
Selection mbar, bar
mmH2O, mH2O
inH2O, ftH2O
Pa, kPa, MPa
psi
mmHg, inHg
kgf/cm
2
Factory setting mbar or bar depending on the nominal measuring range of
the sensor, or as per order specifications.
8.3.2 Pos. zero adjust
Corrected press. (172)
Navigation Setup → Corrected press.
Write permission Operators/Service engineers/Expert
Description Displays the measured pressure after sensor trim and
position adjustment.
Note If this value is not equal to "0", it can be corrected to "0" by
the position adjustment.
Pos. zero adjust (007) (gauge pressure sensors))
Write permission Operator/Maintenance/Expert
Description Pos. zero adjustment – the pressure difference between
zero (set point) and the measured pressure need not be
known.
Example Measured value = 2.2 mbar (0.033 psi)
You correct the measured value via the "Pos. zero adjust"
parameter with the "Confirm" option. This means that you
are assigning the value 0.0 to the pressure present.
Measured value (after pos. zero adjustment) = 0.0 mbar
The current value is also corrected.