Deltabar S FOUNDATION Fieldbus Commissioning
Endress+Hauser 35
6.5.3 Overview of level measurement
Measuring task LEVEL
SELECTION/LE
VEL MODE
Measured
variable options
Description Comment Measured value
display
The measured
variable is in direct
proportion to the
measured pressure.
Calibration is
performed by
entering two
pressure-level
value pairs.
LEVEL
SELECTION: Level
Easy Pressure
Via OUTPUT UNIT
parameter: %, level,
volume or mass
units.
Calibration with
reference
pressure – wet
calibration, see
Operating
Instructions
BA00303P.
–Calibration
without
reference
pressure – dry
calibration, see
Operating
Instructions
BA00303P.
Incorrect entries
are possible
Customized
units are not
possible
The measured
value display and
the LEVEL
BEFORE LIN.
parameter show
the measured
value.
The measured
variable is in direct
proportion to the
measured pressure.
Calibration is
performed by
entering the
density and two
height-level value
pairs.
LEVEL
SELECTION: Level
Easy Height
Via OUTPUT UNIT
parameter: %, level,
volume or mass
units.
Calibration with
reference
pressure – wet
calibration, see
Operating
Instructions
BA00303P.
–Calibration
without
reference
pressure – dry
calibration, see
Operating
Instructions
BA00303P.
Incorrect entries
are possible
Customized
units are not
possible
The measured
value display and
the LEVEL
BEFORE LIN.
parameter show
the measured
value.
The measured
variable is in direct
proportion to the
measured pressure.
LEVEL
SELECTION: Level
standard/
LEVEL MODE:
Linear
Via LIN.
MEASURAND
parameter:
% (level)
Level
Volume
–Mass
Calibration with
reference
pressure – wet
calibration, see
Operating
Instructions
BA00303P.
–Calibration
without
reference
pressure – dry
calibration, see
Operating
Instructions
BA00303P.
Incorrect entries
are rejected by
the device
Customized
level, volume
and mass units
are possible
The measured
value display and
the LEVEL
BEFORE LIN.
parameter show
the measured
value.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Endress+Hauser Deltabar S PMD70 and is the answer not in the manual?

Endress+Hauser Deltabar S PMD70 Specifications

General IconGeneral
BrandEndress+Hauser
ModelDeltabar S PMD70
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals