Deltabar S FOUNDATION Fieldbus Operation
Endress+Hauser 25
• Are all screws firmly tightened?
• Are the housing covers screwed down tight?
As soon as voltage is applied to the device, the green LED on the electronic insert lights up for a
few seconds or the connected onsite display lights up.
6Operation
Feature 20 "Output; operation" in the order code provides you with information on the operating
options available to you.
6.1 Onsite display (optional)
A 4-line liquid crystal display (LCD) is used for display and operation. The onsite display shows
measured values, fault messages and notice messages. The display of the device can be turned
in 90° steps. Depending on the orientation of the device, this makes it easy to operate the device
and read the measured value.
Functions:
• 8-digit measured value display including sign and decimal point, unit display
• Bar graph as graphic display of the current pressure measured value in relation to the set
pressure range in the Pressure Transducer Block. The pressure range is set by means of the
SCALE_IN parameter.
• Easy and complete menu guidance by dividing the parameters into several levels and groups
•Menu guidance
The onsite display is available in English. Needless to say, the device can also be operated in
6 languages (de, en, fr, es, jp, ch) via the DTM or EDD. The FieldCare program is an E+H DTM
operating tool and can be acquired from endress.com.
• Each parameter has a 3-digit ID to aid navigation
• Option of configuring the display according to individual requirements and preferences, such
as alternating display, contrast setting, display of other measured values such as sensor
temperature
• Comprehensive diagnostic functions (fault and warning message, maximum indicator, etc.)
• Rapid and safe commissioning using Quick Setup menus
Versions in the order code Operation
P FOUNDATION Fieldbus; external operation, LCD Via onsite display and 1 key on the exterior of the
device
Q FOUNDATION Fieldbus; internal operation, LCD Via onsite display and 1 key on the inside of the
device
R FOUNDATION Fieldbus; internal operation Without onsite display, 1 key on the inside of the
device