Deltabar S FOUNDATION Fieldbus Commissioning
Endress+Hauser 51
For onsite operation, see also ä 29, Section 6.2.3 "Function of the operating elements –
onsite display connected" and ä 31, Section 6.4 "Local operation – onsite display connected".
7.9 Scaling the OUT parameter
See operating instructions.
GROUP SELECTION
Select MEASURING MODE.
Measuring Mode
Select the Primary Value Type parameter.
MEASURING MODE
Select "Pressure" option.
Primary Value Type
Select "Pressure" option.
GROUP SELECTION
Select QUICK SETUP menu.
POS. ZERO ADJUST
Due to orientation of the device, there may be a shift in
the measured value. You correct the MEASURED VALUE
via the POS. ZERO ADJUST parameter with the "Confirm"
option, i.e. you assign the value 0.0 to the pressure
present.
POS. ZERO ADJUST
Due to orientation of the device, there may be a shift in
the measured value. You correct the MEASURED VALUE
via the POS. ZERO ADJUST parameter with the "Confirm"
option, i.e. you assign the value 0.0 to the pressure
present.
DAMPING VALUE
Enter damping time (time constant ). The damping
affects the speed at which all subsequent elements, such
as the onsite display, measured value and the OUT
Value of the Analog Input Block react to a change in the
pressure.
DAMPING VALUE
Enter damping time (time constant ). The damping
affects the speed at which all subsequent elements, such
as the onsite display, measured value and the OUT
Value of the Analog Input Block react to a change in the
pressure.