Deltabar S FOUNDATION Fieldbus Operation
Endress+Hauser 29
The device is configured for the Pressure measuring mode as standard.
Operation via FF configuration program: In the Pressure Transducer Block, change the
measuring mode by means of the PRIMARY_VALUE_TYPE and LINEARIZATION
parameters.
Operation via digital communication: change the measuring mode by means of the
MEASURING MODE parameter.
You can change the measuring mode by means of the MEASURING MODE parameter.
ä 37, Section 7.4 "Selecting the language and measuring mode".
The pressure applied must be within the nominal pressure limits of the sensor. See
information on the nameplate.
Perform position adjustment:
1. Pressure is present at device.
2. Press key for at least 3 seconds.
3. If the LED on the electronic insert lights up briefly, the pressure applied has been accepted
for position adjustment.
If the LED does not light up, the pressure applied was not accepted. Observe the input
limits. For error messages see operating instructions..
6.2.3 Function of the operating elements – onsite display connected
Key(s) Meaning
O
Navigate upwards in the picklist
Edit numerical values or characters within a function
S
Navigate downwards in the picklist
Edit numerical values or characters within a function
F
–Confirm entry
Go to next item
O
and
F
Contrast setting of onsite display: increase
S
and
F
Contrast setting of onsite display: reduce
O
and
S
ESC functions:
Exit the editing mode without saving the altered value
You are in the menu within a function group: the first time you press the keys
simultaneously, you go back one parameter in the function group. Every subsequent
time you press the keys simultaneously, you go up one level in the menu.
You are in the menu on a selection level: every time you press the keys
simultaneously, you go up one level in the menu.
Note: For the terms function group, level, selection level, ä 31, Section 6.4.1