Deltabar S FOUNDATION Fieldbus Commissioning
Endress+Hauser 37
• "Post-connection check" checklist see Section 5.4
7.3 Commissioning via an FF configuration program
See operating instructions.
7.4 Selecting the language and measuring mode
7.4.1 Local operation
The MEASURING MODE parameter is on the 1st selection level. ä 31, Section 6.4.1 "Menu
structure".
The following measuring modes are available:
• Pressure
• Level
•Flow
7.4.2 Selecting the language and measuring mode by means of the FieldCare operating
program
See operating instructions.
7.5 Position adjustment
Due to the orientation of the device, there may be a shift in the measured value, i.e. when the
container is empty or partly filled, the measured value parameter does not display zero. There
are three options to choose from when performing position adjustment.
• Onsite display menu path: GROUP SELECTION OPERATING MENU SETTINGS
POSITION ADJUSTMENT
• FieldCare menu path: OPERATING MENU SETTINGS POSITION ADJUSTMENT
7.5.1 Performing position adjustment via the onsite display or FieldCare
The parameters listed in the following table can be found in the POSITION ADJUSTMENT group
(menu path: OPERATING MENU SETTINGS POSITION ADJUSTMENT).