Commissioning Deltabar S FOUNDATION Fieldbus
50 Endress+Hauser
7.8.2 Information on differential pressure measurement
• By means of the FieldCare operating program, a Quick Setup menu is available for each of the
measuring modes pressure, level and flow which guides you through the most important basic
functions. With the setting in the MEASURING MODE parameter, you specify which Quick
Setup menu should be displayed. ä 37, Section 7.4 "Selecting the language and measuring
mode". No Quick Setup menus are available for the FF configuration programs.
• For a detailed description of the parameters, see Operating Instructions BA00303P "Cerabar
S/Deltabar S/Deltapilot S, Description of Device Functions"
– FF, Table, Pressure Transducer Block
– FieldCare, Table, POSITION ADJUSTMENT
– FieldCare, Table, BASIC SETUP
– FieldCare, Table, EXTENDED SETUP
Changing the measuring mode affects the span (URV)!
This situation can result in product overflow.
‣ If the measuring mode is changed, the span setting (URV) must be verified in the
"Calibration" "Basic Setup" operating menu and, if necessary, reconfigured!
7.8.3 Quick Setup menu for Pressure measuring mode
P01-xMD7xxxx-19-xx-xx-en-080
Fig. 17: Quick Setup menu for "Pressure" measuring mode
1) 2)1) 2)
1)
1) On-site display only
2) FieldCare only
PROFILE VIEW
POS. ZERO ADJUST
DAMPING VALUE
MEASURED VALUE
QUICK SETUP
GROUP SELECTION
MEASURING MODEMEASURING MODELANGUAGE
FlowPressure Level
OPERATING MENU
Local operation FieldCare
Measured value display
Onsite display: Switch from the measured value display
to GROUP SELECTION with F .
Measured value display
Select QUICK SETUP menu.