Deltabar S FOUNDATION Fieldbus Commissioning
Endress+Hauser 41
7.6.3 Quick Setup menu for the Flow measuring mode (FieldCare)
P01-xxxxxxxx-19-xx-xx-en-166
Fig. 11: Quick Setup menu for the "Flow" measuring mode
1) 1) 2) 2)
1)
1) On-site display only
2) FieldCare only
PROFILE VIEW
MAX FLOW
MAX. PRESS. FLOW
POS. ZERO ADJUST
DAMPING VALUE
MEASURED VALUE
QUICK SETUP
GROUP SELECTION
MEASURING MODE MEASURING MODELANGUAGE
FlowPressure Level
QUICK SETUP OPERATING MENU
Local operation FieldCare
Measured value display
Onsite display: Switch from the measured value display
to GROUP SELECTION with F .
Measured value display
Select QUICK SETUP menu.
GROUP SELECTION
Select MEASURING MODE.
Measuring Mode
Select the Primary Value Type parameter.
MEASURING MODE
Select "Flow" option.
GROUP SELECTION
Select QUICK SETUP menu.
Primary Value Type
Select "Flow" option.
POS. ZERO ADJUST
Due to orientation of the device, there may be a shift in
the measured value. You correct the MEASURED VALUE
via the POS. ZERO ADJUST parameter with the "Confirm"
option, i.e. you assign the value 0.0 to the pressure
present.
POS. ZERO ADJUST
Due to orientation of the device, there may be a shift in
the measured value. You correct the MEASURED VALUE
via the POS. ZERO ADJUST parameter with the "Confirm"
option, i.e. you assign the value 0.0 to the pressure
present.
MAX. FLOW
Enter maximum flow of primary device.
( See also layout sheet of primary device).
MAX. FLOW
Enter maximum flow of primary device.
(See also layout sheet of primary device).