Deltabar S FOUNDATION Fieldbus Commissioning
Endress+Hauser 47
7.7.4 Quick Setup menu for Level measuring mode
Some parameters are only displayed if other parameters are appropriately configured. For
example, the EMPTY CALIB. parameter is only displayed in the following cases:
LEVEL SELECTION "Level Easy Pressure" and CALIBRATION MODE "Wet"
LEVEL SELECTION "Level Standard", LEVEL MODE "Linear" and CALIBRATION MODE "Wet"
You can find the LEVEL MODE and the CALIBRATION MODE parameter in the BASIC
SETTINGS function group.
The following parameters are set to the following values in the factory:
LEVEL SELECTION: Level Easy Pressure
CALIBRATION MODE: Wet
OUTPUT UNIT or LIN. MEASURAND: %
EMPTY CALIB: 0.0
FULL CALIB: 100.0
The quick setup is suitable for simple and quick commissioning. If you wish to make more
complex settings, e.g. change the unit form "%" to "m", you will have to calibrate using the
BASIC SETTINGS group. See Operating Instructions BA00303P.
P01-xMD7xxxx-19-xx-xx-en-079
Fig. 15: Quick Setup menu for "Level" measuring mode
1) 2)1)
1)
2)
1)
3)
3)
EMPTY CALIB.
FULL CALIB.
LEVEL SELECTION
1) On-site display only
2) FieldCare only
3) LEVEL SELECTION "Level Easy Pressure"
and CALIBRATION MODE "Wet"
LEVEL SELECTION = "Level Standard",
LEVEL MODE = "Linear" and
CALIBRATI
ON MODE = "Wet"
PROFILE VIEW
POS. ZERO ADJUST
DAMPING VALUE
MEASURED VALUE
QUICK SETUP
GROUP SELECTION
MEASURING MODEMEASURING MODELANGUAGE
FlowPressure Level
OPERATING MENU