EasyManua.ls Logo

Endress+Hauser Ecograph T RSG30 - Digital I;O and Relay Configurations

Endress+Hauser Ecograph T RSG30
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wiring
16
4.2.4 Digital I/O
4.2.5 Relay
!
Note!
The opening and closing function (= activation or deactivation of the relay coil) in case of a limit
value can be defined in the setup "Setup - Relay"
Type Terminal
(-) (+) 91 92 93
Digital input Digital input 1 Digital input 2 Digital input 3
Auxiliary voltage
output, not stabilized,
max. 250 mA
Ground Approx. + 24 V
DI3
93
92
91
Type Terminal
41 42 31 32 21 22 11 13 12
Alarm
relay 1
Normally
open
contact
(NO)
2)
Changeover
contact
Normally
closed
contact
(NC)
1)
Relay 2 Switching
contact
Normally
open
contact
(NO)
2)
Relay 3 Switching
contact
Normally
open
contact
(NO)
2)
Relay 4 Switching
contact
Normally
open
contact
(NO)
2)
1) NC = normally closed (breaker)
2) NO = normally open (maker)
41
42
31
32
21
22
11
13
12
Rel4 Rel3
Rel2
Rel1

Table of Contents