Operating menu and parameter description iTEMP TMT142B
68 Endress+Hauser
Current output simulation
Navigation Diagnostics → Simulation → Current output simulation
Description Use this function to switch simulation of the current output on and off. The status signal
indicates a category "C" diagnostic message ("function check") while the simulation is
running.
Options Off
On
Factory setting Off
Value current output
Navigation Diagnostics → Simulation → Value current output
Description Use this function to set a current value for the simulation. In this way, users can verify the
correct adjustment of the current output and the correct function of downstream switching
units.
User entry 3.58 to 23 mA
Factory setting 3.58 mA
Sensor simulation
Navigation Diagnostics → Simulation → Sensor simulation
Description Use this function to enable the simulation of the process variable. The simulation value of
the process variable is defined in the Sensor simulation value parameter. The status
signal indicates a category "C" diagnostic message ("function check") while the simulation is
running.
Options Off
On
Factory setting Off
Sensor simulation value
Navigation Diagnostics → Simulation → Sensor simulation value