iTEMP TMT142B Operating menu and parameter description
Endress+Hauser 75
Description Displays the tertiary device variable.
QV
Navigation Application → Measured values → QV
Description Displays the quaternary (fourth) device variable.
14.2.2 Submenu: Sensor
Unit
Navigation Application → Sensor → Unit
Description Use this function to select the engineering unit for all the measured values.
Selection • °C
• °F
• K
• Ω
• mV
Factory setting °C
Additional information Please note: If another unit has been selected instead of the factory setting (°C), all
the set temperature values are converted to correspond to the configured
temperature unit.
Example: 150 °C is set as the upper range value. Following the selection of °F as the
engineering unit, the new (converted) upper range value = 302 °F.
Sensor type
Navigation Application → Sensor → Sensor type
Description Use this function to select the sensor type for the sensor input.
Please observe the terminal assignment when connecting the sensors.
Selection A list of all the possible sensor types is provided in the 'Technical data' section. → 47
Factory setting Pt100 IEC751
Connection type