iTEMP TMT142B Operating menu and parameter description
Endress+Hauser 79
User entry Depends on the sensor type selected.
Factory setting Depends on the sensor type selected.
Sensor upper limit
Navigation Application → Sensor → Linearization → Sensor upper limit
Prerequisite The RTD platinum, RTD poly nickel or RTD copper polynomial option is enabled in the
Sensor type parameter.
Description Use this function to set the upper calculation limit for special sensor linearization.
User entry Depends on the sensor type selected.
Factory setting Depends on the sensor type selected.
14.2.4 Submenu: Current output
4mA value
Navigation Application → Current output → 4mA value
Description Use this function to assign a measured value to the current value 4 mA.
Factory setting 0 °C
20mA value
Navigation Application → Current output → 20mA value
Description Use this function to assign a measured value to the current value 20 mA.
Factory setting 100 °C
Failure mode
Navigation Application → Current output → Failure mode
Description Use this function to select the signal on alarm level of the current output in the event of an
error.