Levelflex FMP53
Endress+Hauser 13
Protocol-specific data HART
Manufacturer ID 17 (0x11)
Device type ID 0x1122
HART specification 7.0
Device description files (DTM, DD) Information and files under:
• www.endress.com
• www.fieldcommgroup.org
HART load min. 250 Ω
HART device variables The measured values can be freely assigned to the device variables.
Measured values for PV (primary variable)
• Level linearized
• Distance
• Electronic temperature
• Relative echo amplitude
Measured values for SV, TV, QV (second, third and fourth variable)
• Level linearized
• Distance
• Terminal voltage
• Electronic temperature
• Absolute echo amplitude
• Relative echo amplitude
• Calculated ε
r
value
Supported functions • Burst mode
• Additional transmitter status
Wireless HART data
Minimum starting voltage 17.5 V
Start-up current 4 mA
Starting time 80 s
Minimum operating voltage 17.5 V
Multidrop current 4.0 mA
Time for connection setup 30 s