Levelflex FMP53
82 Endress+Hauser
Customer-specific
configuration
If the option IJ: "Customized parameterization HART", IK "Customized parameterization PA" or IL
"Customized parameterization FF" has been selected in feature 570 "Service", presettings that differ
from the default settings can be selected for the following parameters:
Parameter Communication
protocol
Picklist / range of values
Setup → Unit of length • HART
• PA
• FF
• in
• ft
• mm
• m
Setup → Empty calibration • HART
• PA
• FF
0 to 6 m (0 to 18 ft)
Setup → Full calibration • HART
• PA
• FF
0 to 6 m (0 to 18 ft)
Setup → Extended setup → Curr. output 1/2 → Damping HART 0 to 999.9 s
Setup → Extended setup → Curr. output 1/2 → Failure
mode
HART • Min
• Max
• Last valid value
Expert → Comm. → HART config. → Burst mode HART • Off
• On
Tagging (TAG)
Ordering feature 895: Marking
Option Z1: Tagging (TAG), see additional spec.
Position of the measuring
point marking
To be selected in the additional specifications:
• Tag plate Stainless Steel
• Self-adhesive paper label
• Supplied label/plate
• RFID TAG
• RFID TAG + Tag plate Stainless Steel
• RFID TAG + Self-adhesive paper label
• RFID TAG + Supplied label/plate
Definition of the measuring
point designation
To be defined in the additional specifications:
3 lines containing up to 18 characters each
The measuring point designation appears on the selected label and/or the
RFID TAG.
Designation in the Electronic
Name Plate (ENP)
The first 32 characters of the measuring point designation
Designation on the display
module
The first 12 characters of the measuring point designation
Application packages
Heartbeat Diagnostics Availability
Available in all device versions.
Function
• Continuous self-monitoring of the device.
• Diagnostic messages output to
• the local display.
• an asset management system (e.g. FieldCare/DeviceCare).
• an automation system (e.g. PLC).