Levelflex FMP53
Endress+Hauser 45
Operating conditions: Environment
Ambient temperature
Measuring device –20 to +80 °C (–4 to +176 °F)
Local display –20 to +70 °C (–4 to +158 °F), the readability of the display may be impaired at
temperatures outside the temperature range.
Connecting cable (for
"Sensor, remote" probe
design)
Max. 150 °C (302 °F)
Remote display FHX50 –40 to 80 °C (–40 to 176 °F)
For outdoor operation in strong sunlight:
Mount the device in the shade.
Avoid direct sunlight, particularly in warm climatic regions.
Use a weather protection cover (see accessories).
Ambient temperature limits
The following diagrams only consider functional aspects. Additional restrictions may apply for
certified device versions. See the separate Safety Instructions for more information.