EasyManua.ls Logo

Endress+Hauser Levelflex FMP53 - Page 19

Endress+Hauser Levelflex FMP53
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Levelflex FMP53
Endress+Hauser 19
Terminal assignment 2-wire: 4-20 mA HART, switch output
1
3
+
+
2
4
-
-
B
1
4
5
2
3
A0036500
 6 Terminal assignment 2-wire: 4-20 mA HART, switch output
A Without integrated overvoltage protection
B With integrated overvoltage protection
1 Connection 4-20 mA HART passive: terminals 1 and 2, without integrated overvoltage protection
2 Connection switch output (Open Collector): terminals 3 and 4, without integrated overvoltage protection
3 Connection switch output (Open Collector): terminals 3 and 4, with integrated overvoltage protection
4 Connection 4-20 mA HART passive: terminals 1 and 2, with integrated overvoltage protection
5 Terminal for cable screen
Block diagram 2-wire: 4-20 mA HART, switch output
5
4
1
2
3
+
+
+
-
-
-
Y
I
6
7
1
2
3
4
A0036501
 7 Block diagram 2-wire: 4-20 mA HART, switch output
1 Active barrier with power supply (e.g. RN221N); observe terminal voltage
2 HART communication resistor (≥ 250 Ω); observe maximum load
3 Connection for Commubox FXA195 or FieldXpert SFX350/SFX370 (via VIATOR Bluetooth modem)
4 Analog display device; observe maximum load
5 Cable screen; observe cable specification
6 Measuring device
7 Switch output (Open Collector)

Table of Contents

Other manuals for Endress+Hauser Levelflex FMP53

Related product manuals