Additional conditions
• When mounting outdoors, a weather protection cover (1) can be used to protect the device against
extreme weather conditions.
• Do not mount the probe in the filling curtain (2).
When the housing is mounted in a recess (e.g. in a concrete ceiling), observe a minimum
distance of 100 mm (4 in) between the cover of the connection compartment/electronics
compartment and the wall. Otherwise the connection compartment/electronics compartment
will not be accessible after installation.