Liquiline CM442R/CM444R/CM448R Electrical connection
Endress+Hauser 37
6.5.3 Bus termination
There are two ways to terminate the bus:
1. Internal terminating resistor (via DIP switch on the module board)
Using a suitable tool, such as a tweezers, set all 4 DIP switches to the "ON" position.
The internal terminating resistor is used.
a0016306
Fig. 46: Structure of the internal terminating resistor
2. External terminating resistor
Here, leave the DIP switches on the module board in the "OFF" position (factory setting).
Connect the resistor to terminals 81 and 82 on the front of module 485 for 5-V power
supply.
The external terminating resistor is used.
Fig. 45: DIP switches for internal terminating resistor