Liquiphant FTL64
Endress+Hauser 19
Batteries
The battery is categorized as dangerous goods when transported by air and may not be installed
in the device when shipped.
Replacement batteries can be purchased from a specialist retailer. Only the following types of
AA 3.6 V lithium batteries made by the manufacturers listed below are suitable as replacement
batteries:
SAFT LS14500
TADIRAN SL-360/s
XENOENERGY XL-060F
Special battery in conjunction with electronic insert FEL68 (2-wire NAMUR)
For energy-related reasons, the Bluetooth module VU121 requires a special battery when operated
with electronics insert FEL68 (2-wire NAMUR).
The service life of the Bluetooth module without replacing the battery is at least 5 years with a
maximum of 60 downloads of complete datasets (at ambient temperatures between
10 to 40 °C (50 to 104 °F)).
Approvals
The Bluetooth module is approved for use in the following types of protection for devices: Ex i, Ex d,
Ex e or Ex t. The temperature class of the device is limited to T4  to  T1 if the Bluetooth module is
used in type of protection Ex i /IS in conjunction with electronic insert FEL68 (2-wire NAMUR) and
the required battery in the Bluetooth module.
Additional technical data
Free-field range: 50 m (165 ft) max.
Operation radius with intervisibility around the device: 10 m (33 ft)
For documentation on radio approvals, see the Endress+Hauser website: www.endress.com
Downloads.
Functions
 Additional details in the "Operability" section.
Heartbeat Technology Heartbeat Technology module
The software package consists of 3 modules. These three modules combined check, evaluate and
monitor device functionality and process conditions.
Heartbeat Diagnostics
Heartbeat Verification
Heartbeat Monitoring
 For more detailed information, see the "Application packages" section.
Performance characteristics
Reference operating
conditions
Ambient temperature:+23 °C (+73 °F)
Process temperature: +23 °C (+73 °F) ±5 °C (9 °F)
Density (water): 1 g/cm
3
Medium viscosity: 1 mPa⋅s
Process pressure: unpressurized
Sensor installation: vertically from above
Density selection switch: > 0.7 g/cm
3
(SGU)
Switch direction of sensor: uncovered to covered
Take switch point into consideration
The following are typical switch points, depending on the orientation of the point level switch.