Liquiphant FTL64
30 Endress+Hauser
!101 (3.98)
118 (4.65)
A0035590
 33 Single compartment 316L, cast; with Ex d/XP approval also; Product Configurator: order code for
"Housing; material", option C. Unit of measurement mm (in)
131 (5.16)
163 (6.42)
!147 (5.79)
!
101 (3.98)
A0035591
 34 Dual compartment, L-shaped; aluminum, coated; with Ex d/XP approval also; Product Configurator: order
code for "Housing; material", option M. Unit of measurement mm (in)
Ground terminal
Ground terminal inside the housing, max. conductor cross-section 2.5 mm
2
(14 AWG)
Ground terminal outside the housing, max. conductor cross-section 4 mm
2
(12 AWG)
If safety extra-low voltage is used to supply power to electronic inserts, do not connect protective
ground
Cable glands
Cable diameter:
Plastic: ø5 to 10 mm (0.2 to 0.38 in)
Nickel-plated brass: ø7 to 10.5 mm (0.28 to 0.41 in)
Stainless steel: ø7 to 12 mm (0.28 to 0.47 in)
The scope of delivery comprises:
1 cable gland installed
1 cable gland sealed with dummy plug
A second cable gland (not installed) is also included in the scope of delivery of the relay
electronics.
Exceptions: With Ex d/XP, only threaded entries are permitted.
Temperature spacer
Provides sealed insulation for the vessel and a normal ambient temperature for the housing
In the event of damage to the sensor, protects the housing from exposure to vessel pressures up to
100 bar (1 450 psi)