EasyManua.ls Logo

Endress+Hauser Liquistation CSF33 - Terminal Assignment for Input;Output; Signals; Ensuring the Degree of Protection

Endress+Hauser Liquistation CSF33
180 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical connection Liquistation CSF33
28 Endress+Hauser
145
146
-
-
+
+
A0013407
 25 Binary output with external voltage source
When connecting to an internal voltage source, use the terminal connection on the rear of
the dosing compartment. The connection is located on the lower terminal strip (on the far
left, + and -) (→  23)
6.3 Terminal assignment for input/output signals
Input signals
2 analog signals 0/4 to 20 mA
2 binary signals > 100 ms pulse width or edge
Output signals
2 binary signals > 1 s pulse width or edge
6.4 Ensuring the degree of protection
Only the mechanical and electrical connections which are described in these instructions
and which are necessary for the required, designated use, may be carried out on the device
delivered.
Exercise care when carrying out the work.
Individual types of protection permitted for this product (impermeability (IP), electrical
safety, EMC interference immunity, Ex protection) can no longer be guaranteed if, for
example :
Covers are left off
Different power units to the ones supplied are used
Cable glands are not sufficiently tightened (must be tightened with 2 Nm (1.5 lbf ft) for
the permitted level of IP protection)
Unsuitable cable diameters are used for the cable glands
Modules are not fully secured
The display is not fully secured (risk of moisture entering due to inadequate sealing)
Loose or insufficiently tightened cables/cable ends
Conductive cable strands are left in the device

Table of Contents

Other manuals for Endress+Hauser Liquistation CSF33

Related product manuals