Liquisys M CLM223/253 Commissioning
Endress+Hauser 47
Coding Field Range of
adjustment
(factory settings
in bold)
Display Info
O311 Select current
range
4 to 20mA
0 to 20 mA
A0025030-EN
O312 0/4 mA value:
Enter the
associated
measured value
Cond/ind: 0.00
μS/cm
MOhm:
0.00kΩ*cm
Conc: 0.00 %
Temp: 0.00 °C
A0025034-EN
Here you can enter the
measured value at which the
min. current value (0/4 mA)
is applied at the transmitter
output (not for controller).
(Turndown see Technical
data.)
O313 20 mA value:
Enter the
associated
measured value
Cond/ind: 2000
μS/cm
MOhm: 500
kΩ*cm
Conc: 99.99 %
Temp: 150 °C
A0025035-EN
Here you can enter the
measured value at which the
max. current value (20 mA) is
applied at the transmitter
output (not for controller).
(Turndown see Technical
data.)
O3 (2) Simulate current
output
Lin = linear (1)
Sim = simulation
(2)
Tab = table (3)
A0025039-EN
Simulation is not ended until
O3(1) or O3(3) is selected.
For further characteristics, see
O3 (1), O3 (3).
O321 Enter simulation
value
Current value
0.00 to 22.00 mA
A0025040-EN
Entering a current value
results in this value being
directly output at the current
output.
O3 (3) Enter current
output table
Lin = linear (1)
Sim = simulation
(2)
Tab = table (3)
A0025041-EN
Only for Plus Package
Values can also be
subsequently added or
modified. The values entered
are automatically sorted by
increasing current value.
For further characteristics, see
O3 (1), O3 (2).
O331 Select table
option
Read
Edit
A0025042-EN
O332 Enter number of
table value pairs
1
1 to 10
A0025043-EN
Enter the number of pairs of x
and y values (measured value
and current value) here.