Micropilot FMR60B PROFINET with Ethernet-APL Electrical connection
Endress+Hauser 19
Cable outer diameter
The cable outer diameter depends on the cable gland used
• Coupling, plastic:
⌀5 to 10 mm (0.2 to 0.38 in)
• Coupling, nickel-plated brass:
⌀7 to 10.5 mm (0.28 to 0.41 in)
• Coupling, stainless steel:
⌀7 to 12 mm (0.28 to 0.47 in)
11.2.3 Overvoltage protection
The overvoltage protection can optionally be ordered as a "Mounted accessory" via the product
structure
Devices without optional overvoltage protection
The equipment fulfills the requirements of the product standard IEC / DIN EN 61326-1 (Table
2 Industrial Environment).
Depending on the type of port (DC power supply, input/output port) different testing levels
according to IEC / DIN EN 61326-1 against transient overvoltages (Surge) are applied (IEC /
DIN EN 61000-4-5 Surge):
Test level on DC power ports and input/output ports is 1 000 V line to earth
Devices with optional overvoltage protection
• Spark-over voltage: min. 400 V
DC
• Tested according to IEC / DIN EN 60079-14 sub chapter 12.3 (IEC / DIN EN 60060-1
chapter 7)
• Nominal discharge current: 10 kA
NOTICE
Device could be destroyed
‣
Always ground device with integrated overvoltage protection.
Overvoltage category
Overvoltage category II