Proline Promag 50H, 53H
6 Endress+Hauser
FOUNDATION Fieldbus interface
FOUNDATION Fieldbus H1
Transmission technology (Physical Layer): IEC 61158-2 (MBP), galvanically isolated
ITK version 5.01
Current consumption: 12 mA
Error current FDE (Fault Disconnection Electronic): 0 mA
Bus connection with integrated reverse polarity protection
Function blocks:
5 × Analog Input (execution time: 18 ms each)
1 × PID (25 ms)
1 × Digital Output (18 ms)
1 × Signal Characterizer (20 ms)
1 × Input Selector (20 ms)
1 × Arithmetic (20 ms)
1 × Integrator (18 ms)
Output data: volume flow, calculated mass flow, temperature, totalizer 1 to 3
Input data: positive zero return (ON/OFF), reset totalizer
Link Master (LM) functionality is supported
Signal on alarm Current output failure response selectable (e.g. in accordance with NAMUR recommendation NE 43)
Pulse/frequency output failure response selectable
Status output (Promag 50) non-conductive by fault or power supply failure
Relay output (Promag 53) de-energized by fault or power supply failure
Load see "Output signal"
Low flow cutoff Switch points for low flow cutoff are selectable.
Galvanic isolation All circuits for inputs, outputs and power supply are galvanically isolated from each other.
Switching output Status output (Promag 50, Promag 53)
Open collector, max. 30 V DC / 250 mA, galvanically isolated.
Configurable for: error messages, Empty Pipe Detection (EPD), flow direction, limit values.
Relay outputs (Promag 53)
Normally closed (NC or break) or normally open (NO or make) contacts available
(default: relay 1 = NO, relay 2 = NC), max. 30 V / 0,5 A AC ; 60 V / 0,1 A DC, galvanically isolated.
Configurable for: error messages, Empty Pipe Detection (EPD), flow direction, limit values, batching contacts.