Proline Prosonic Flow B 200 HART Commissioning
Endress+Hauser 67
Parameter overview with brief description
Parameter Prerequsite Description Selection / User
entry
Factory setting
Assign current output – Select process variable for
current output.
• Off
• Mass flow
• Volume flow
• Corrected volume
flow
• Corrected methane
volume flow
*
• Temperature
*
• Energy flow
*
• Methane fraction
*
• Calorific value
*
• Wobbe index
*
• Sound velocity
• Flow velocity
• Acceptance rate
• Signal asymmetry
• Turbulence
• Signal strength
• Signal to noise
ratio
Volume flow
Current span – Select current range for
process value output and
upper/lower level for alarm
signal.
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• Fixed current
Country-specific:
• 4...20 mA NAMUR
• 4...20 mA US
4 mA value One of the following options is
selected in the Current span
parameter (→ 67):
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
Enter 4 mA value. Signed floating-point
number
Country-specific:
• 0 m³/h
• 0 ft³/min
20 mA value One of the following options is
selected in the Current span
parameter (→ 67):
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
Enter 20 mA value. Signed floating-point
number
Depends on country
and nominal
diameter
Fixed current The Fixed current option is
selected in the Current span
parameter (→ 67).
3.59 to 22.5 mA 4 mA