Commissioning Proline Prosonic Flow B 200 HART
68 Endress+Hauser
Parameter Prerequsite Description Selection / User
entry
Factory setting
Failure mode One of the following options is
selected in the Assign current
output parameter (→  67):
Mass flow
Volume flow
Corrected volume flow
Corrected methane volume
flow
*
Temperature
Energy flow
*
Methane fraction
*
Calorific value
*
Wobbe index
*
Sound velocity
Flow velocity
Acceptance rate
*
Signal asymmetry
*
Turbulence
*
Signal strength
*
Signal to noise ratio
*
One of the following options is
selected in the Current span
parameter (→  67):
4...20 mA NAMUR
4...20 mA US
4...20 mA
Define output behavior in
alarm condition.
Min.
Max.
Last valid value
Actual value
Defined value
Max.
Failure current The Defined value option is
selected in the Failure mode
parameter.
Enter current output value in
alarm condition.
3.59 to 22.5 mA 22.5 mA
* Visibility depends on order options or device settings
10.4.6 Configuring the pulse/frequency/switch output