Commissioning Proline Prosonic Flow B 200 HART
68 Endress+Hauser
Parameter Prerequsite Description Selection / User
entry
Factory setting
Failure mode One of the following options is
selected in the Assign current
output parameter (→ 67):
• Mass flow
• Volume flow
• Corrected volume flow
• Corrected methane volume
flow
*
• Temperature
• Energy flow
*
• Methane fraction
*
• Calorific value
*
• Wobbe index
*
• Sound velocity
• Flow velocity
• Acceptance rate
*
• Signal asymmetry
*
• Turbulence
*
• Signal strength
*
• Signal to noise ratio
*
One of the following options is
selected in the Current span
parameter (→ 67):
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
Define output behavior in
alarm condition.
• Min.
• Max.
• Last valid value
• Actual value
• Defined value
Max.
Failure current The Defined value option is
selected in the Failure mode
parameter.
Enter current output value in
alarm condition.
3.59 to 22.5 mA 22.5 mA
* Visibility depends on order options or device settings
10.4.6 Configuring the pulse/frequency/switch output
The Pulse/frequency/switch output wizard guides you systematically through all the
parameters that can be set for configuring the selected output type.