Proline Prosonic Flow B 200 HART Commissioning
Endress+Hauser 81
Navigation
"Setup" menu → Output conditioning
Structure of the "Output conditioning" wizard
Mode output 2
Rev. flow comp.
Forward flow
Forward/Reverse
End of wizard
Display damping
Damping out. 2
Damping out. 1
Mode output 1
A0015993-EN
26 "Output conditioning" wizard in the "Setup" menu
Parameter overview with brief description
Parameter Prerequsite Description User entry /
Selection
Factory setting
Display damping – Set display reaction time to
fluctuations in the measured
value.
0.0 to 999.9 s 3.0 s
Damping output 1 – Set the reaction time of the
output signal of the current
output to fluctuations in the
measured value.
0 to 999.9 s 1 s
Damping output 2 The measuring device has a
second current output.
Set the reaction time of the
output signal of the second
current output to fluctuations
in the measured value.
0 to 999 s 1 s
Damping output 2 The measuring device has a
pulse/frequency/switch
output.
Set the reaction time of the
output signal of the frequency
output to fluctuations in the
measured value.
0 to 999 s 1 s
Measuring mode output 1 – Select measuring mode for
output.
• Forward flow
• Forward/Reverse
flow
• Reverse flow
compensation
Forward flow
Measuring mode output 2 – Select measuring mode for
output.
• Forward flow
• Forward/Reverse
flow
• Reverse flow
compensation
Forward flow