EasyManua.ls Logo

Endress+Hauser Proline Prosonic Flow P 500 - Mounting Procedures; Mounting Requirements and Considerations; Mounting Position Details

Endress+Hauser Proline Prosonic Flow P 500
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Proline Prosonic Flow P 500
Endress+Hauser 19
Modbus RS485
Physical interface RS485 in accordance with EIA/TIA-485 standard
Terminating resistor Integrated, can be activated via DIP switches
Current output 4 to 20 mA
Order code "Output; input 2" (21)or "Output; input 3" (022):
Option B: current output 4 to 20 mA
Signal mode Can be set to:
Active
Passive
Current span Can be set to:
4 to 20 mA NAMUR
4 to 20 mA US
4 to 20 mA
0 to 20 mA (only if the signal mode is active)
Fixed current
Maximum output values 22.5 mA
Open-circuit voltage DC 28.8 V (active)
Maximum input voltage DC 30 V (passive)
Load 0 to 700 Ω
Resolution 0.38 µA
Damping Configurable: 0 to 999.9 s
Assignable measured
variables
Volume flow
Mass flow
Sound velocity
Flow velocity
Electronics temperature
The range of options increases if the measuring device has one or more
application packages.
Current output 4 to 20 mA Ex i passive
Order code "Output; input 2" (21), "Output; input 3" (022):
Option C: current output 4 to 20 mA Ex i passive
Signal mode Passive
Current span Can be set to:
4 to 20 mA NAMUR
4 to 20 mA US
4 to 20 mA
Fixed current
Maximum output values 22.5 mA
Maximum input voltage DC 30 V
Load 0 to 700 Ω
Resolution 0.38 µA
Damping Configurable: 0 to 999 s
Assignable measured
variables
Volume flow
Mass flow
Sound velocity
Flow velocity
Electronics temperature
The range of options increases if the measuring device has one or more
application packages.

Table of Contents

Other manuals for Endress+Hauser Proline Prosonic Flow P 500

Related product manuals