Proline Prosonic Flow P 500
Endress+Hauser 7
The sensors can be arranged in different ways:
Mounting arrangement for measurement with 1 sensor set (1 measuring path):
The sensors are located on opposite sides of the pipe (offset at 180°): measurement with 1 or 3
traverses
The sensors are located on the same side of the pipe: measurement with 2 or 4 traverses
Mounting arrangement for measurement with 2 sensor sets (2 measuring paths):
1 sensor of each sensor set is located on the opposite side of the pipe (offset at 180°):
measurement with 1 or 3 traverses
The sensors are located on the same side of the pipe: measurement with 2 or 4 traverses
The sensor sets are arranged on the pipe, offset by 90°.
Using 5 MHz sensors
Here, the rails of the two sensor sets are always arranged at an angle of 180° to one another
and connected by cables for all measurements with 1, 2, 3 or 4 traverses. The sensor functions
are assigned in the two rails via the transmitter electronics unit depending on the selected
number of traverses. It is not necessary to swap the cables in the transmitter between the
channels.
Single-path measurement (1 sensor set)
Vertical mounting
A0042013
 2 1 traverse
A0042014
 3 2 traverses
Horizontal mounting
>30°
A0044304
>30°>30°
A0044305
Two-path measurement (2 sensor sets)
Vertical mounting
A0042016
 4 1 traverse
A0042017
 5 2 traverses