Prosonic M - FOUNDATION Fieldbus Installation
Endress+Hauser 21
3.3 Installation conditions
3.3.1 Installation conditions for level measurements
L00-FMU4xxxx-17-00-00-yy-005
Do not install the sensor in the middle of the tank (3). We recommend leaving a distance between
the sensor and the tank wall (1) measuring 1/6 of the tank diameter.
Use a protective cover, in order to protect the device from direct sun or rain (2).
Avoid measurements through the filling curtain (4).
Make sure that equipment (5) such as limit switches, temperature sensors, etc. are not located
within the emitting angle . In particular, symmetrical equipment (6) such as heating coils, baffles
etc. can influence measurement.
Align the sensor so that it is vertical to the product surface (7).
Never install two ultrasonic measuring devices in a tank, as the two signals may affect each other.
To estimate the detection range, use the 3 dB emitting angle .
3.3.2 Installation in narrow shafts
Sensor L
max
r
max
FMU40 11° 5 m (16 ft) 0.48 m (1.6 ft)
FMU41 11° 8 m (26 ft) 0.77 m (2.5 ft)
FMU42 10 m (33 ft) 0.79 m (2.6 ft)
FMU43 15 m (49 ft) 0.79 m (2.6 ft)
FMU44 11 ° 20 m (66 ft) 1.93 m (6.3 ft)
In narrow shafts with strong interference
echoes, we recommend using an ultrasound
guide pipe (e.g. PE or PVC wastewater pipe)
with a minimum diameter of 100 mm (3.94 in).
Make sure that the pipe is not soiled by accumu-
lated dirt. If necessary, clean the pipe at regular
intervals.
L00-FMU4xxxx-17-00-00-yy-010